Motor-driven Multi-Burner igniter control. Automatically fires up to 40 burners in seconds!
Features:
Improved Safety and Performance:
One unit automatically fires up a complete network of gas burners in ovens,
furnaces, boilers and heat treating systems.
High-Speed Spark Ignition:
40 burners within 3 seconds
No Spark Gap Loss:
Positive contact-wiper switching design eliminates arcing gap and wasted
energy. - puts full voltage spark at burner!
Interchangeable Components:
When systems are enlarged, Rotor unit and spark electrode end plates can
be replaced with higher capacity units to accommodate additional burners.
How it works
When the Ignitifier is energized by a START button, a motorized double-end
shaft rotates its wiping contact against a series of stationary contact tips
(one for each Ignitor in the system). This causes a high voltage impulse from an
ignition transformer to be fed to each burner spark electrode, and immediately
ignites the gas-air mixture of each burner position (gas-air mixture has been
simultaneously released with actuation of the START button). The unit repeats
until all burners are ignited.
Printable Literature
Ignitifier I 5909N Brochure

Solid-State Multiple Ignition System.
Features One-Wire Distribution:
One single compact unit ignites up to 30 (or more) spark ignited gas burners
all at the same time and instaneously.
Features:
All Electric
Instantaneous
Dependable
Low Primary Current for many burners
No need for special high current switches,
contactors or power supply
No mechanical action
No need for multiplicity of complex high voltage wiring; requires only single wire service to electrical box or similar connections. For ovens, furnaces, boilers, etc.
Compare to rotary and other mechanical systems:
Solid-state dependability, compactness
Can be installed for continuous operation
No moving parts, no mechanical wear
Instant, simultaneous sparking at all
points
Ignites unbalanced mixtures more
effectively
Saves on equipment installation time
Less space, less wiring, less conduit
Maintenance practically eliminated
Simple, quality components
Printable Literature
Ignitifier II 6954 Brochure

Features Spark Blind Ignitor (single burner)
Form 7759 Ignitifier III Spark Blind Ignitor may be used with all
models of Protectofier combustion safeguards, operating in conjuction with P-CII
ultraviolet scanners to avoid false sensing indication resulting from ignition
spark. The Ignitifier III is to be used as a source of electric spark only and is not
intended for use as a safety device.
Printable Literature
Ignitifier III 7759 Brochure

Detects any flame which contains ultra-violet
Features:
High flame signal
Can be mounted in any position
Encapsulated sensor tube permanently
sealed in gas tight housing
Operates with gas and/or oil flames
P-C II
Basic model.
Provided with an electrical connector for
flexible metal conduit (3/8" max.)
P-C II W
Provided with 1/2" straight liquid-tite
electrical connector.
P-C II WRA
Provided with a 1/2" right angle liquid-tite
electrical connector.
Printable Literature
P-C II Brochure

Protectal Unified Features
Ready to install
No additional components necessary
Prewired for immediate operation
Protectal Unified 62019
Form 6642VA Protectofier*
Plug-in solid state electronic FLAME-PAK
Plug-in ACF relays
START pushbutton
Signal light to indicate flame
Ignition transformer (optional)
Dust-tight steel enclosure
*Available options include Form "B" Protectofier for automatic operation and safety requirements such as non-relight, low fire start, and interrupted pilot.
Protectal Unified 62021
Form 6642VT Protectofier with plug-in
TIMOFIER for purge and ignition trial,
plug-in solid state electronic FLAME-PAK
and plug-in ACF relays
Burner Off/Run/Ignition switch
Signal light to indicate flame
Signal light to indicate timer operation
Ignition transformer (optional)
Dust-tight steel enclosure
*Available options include Form "B" Protectofier for automatic operation and safety requirements such as non-relight, low fire start, and interrrupted pilot.
Standard Complete Unified 82064 and 82065
Compact Control Panel with same features as Unified Panel - plus Motor Control
Complete Unified 63031 and 63032
Compact Control Panel with same features as Standard Complete Unified Panel - except customized to perform a wide range of additional control functions.
Printable Literature
Protectal Unified Control Panels Brochure

Operate with Flame Rod and/or P-C II Scanner
6642 Features
Modularized Multi-Burner Control
Time Proven Plug-in Solid State FLAME-PAK
Amplifier
Plug-in, Interchangeable Relays
Plug-in Power Transformer
Flame Rod and/or Ultra-Violet Sensing.
Independent or simultaneously using
same FLAME-PAK Amplifier.
Form 6642VA
Basic combustion safeguard model
Form 6642VB
Breaker - lockout switch model
Required for automatic lighted
installations. System "latches out" after
failure to light within ignition trial time
and cannot attempt restart until switch is
manually reset.
Standard ignition trial time is 15 seconds.
Also available in 10-second and 5-second
trial time.
Form 6642VBNR - Automatic only and
Non-relight.
Form 6642VL
Load relay - included for all multi-burner
models
Form 6642VT
Timofier model plugin, fixed time
assembly.
The timofier provides purge time and
ignition trial time. The ignition trial time is
deducted from the motor time cycle
(1/2, 1, 1-1/4, 2, 3, 4, and 6 minutes
available for manual and automatic
models; 10 minutes for manual model
only) to purge the time.
Standard ignition trial time is 15 seconds.
Also available in 10-second and 5-second
trial time.
Specify both purge and ignition times.
Purge time shall allow system to have a
minimum of four fresh air changes.
Form 6642VBL
Combines features of Breaker and Load
relay models described above.
Form 6642VBLNR - Automatic only and
Non-relight.
Form 6642VBT
Combines features of Breaker and
Timofier models described above.
Form 6642VBTNR - Automatic only and
Non-relight.
Form 6642VLT
Combines features of Load relay
and Timofier models described above.
Form 6642VBLT
Combines features of Breaker, Load relay,
and Timofier models described above.
Form 6642VBLTNR - Automatic only and
Non-relight.
Form 6642FF
Full Feature Combustion Safeguard
including:
Proof of Closure
Proof of High Fire Purge
Purge Timing (In 15 sec. increments,
7 min. 45 sec. max)
Proof of Low Fire Start
Ignition Trial Timing (Pilot) 10 sec.
Pilot Interrupt Timing
(Main burner ignition trial) 10 or 15 sec.
Alarm output if the safety interlocks
(limit switches) or flame failure
causes shutdown.
Relay contacts available to drive actuator
to high fire for purge, low fire for
ignition trial, and control when main
burner is proven.
Eight status lights
Printable Literature
Protectofier 6642 Brochure
Form 6642VA
Form 6642VB
Form 6642VBNR
Form 6642VL
Form 6642VT
Form 6642VBL
Form 6642VBLNR
Form 6642VBT
Form 6642VBTNR
Form 6642VLT
Form 6642VBLT
Form 6642VBLTNR
Form 6642FF

Operate with Flame Rod and/or P-C II Scanner
7256 Features
Compact Design - Single Burner
Time Proven Plug-in Solid State FLAME-PAK
Amplifier
Plug-in, Interchangeable Relays
Plug-in Power Transformer
Flame Rod and/or Ultra-Violet Sensing.
Independent or simultaneously using
same FLAME-PAK Amplifier.
Form 7256-AH/AHE
Basic manual model
"E" indicates enclosed model
Form 7256-B/BE
Manual or automatic operation
Recycle on flame failure automatic.
Select ignition trial timing cycle:
15 sec.(standard), 5 sec. or 10 sec.
"E" indicates enclosed model
Form 7256-BH/BHE
"H" indicates flame failure alarm
Recycle on flame failure automatic.
Select ignition trial timing cycle:
15 sec.(standard), 5 sec. or 10 sec.
"E" indicates enclosed model
Form 7256-BNRE/BNRHE
"NR" indicates automatic models with
additional relay to prevent relight
attempt on flame failure.
Select ignition trial timing cycle:
15 sec.(standard), 5 sec. or 10 sec.
"E" indicates enclosed model
Form 7256-BTNRE/BTNRHE
"T" indicates plug-in "SST" purge timer
provided for fixed pre-purged cycle.
Select purge cycle: 15, 30, 60 or 90 sec.
Select ignition trial timing cycle:
15 sec.(standard), 5 sec. or 10 sec.
"E" indicates enclosed model
Printable Literature
Protectofier 7256 Brochure
Form 7256-B/BE
Form 7256-BH/BHE
Form 7256-BNRE/BNRHE
Form 7256-BTNRE/BTNRHE

Unequalled reliability and operating savings for monitoring equipment in heating and processing systems. Monitors up to 8 read-out positions.
Features
Single Wire Connections
No Additional Relays
Compact Design 1/4 Din Size
Start-Up Status Display
First-Outage Readout
Power Interruption Indicator
Lights and Pushbuttons
Strart-up Lights indicate all monitored
open limits when power is applied or when
reset button is pressed.
First-out Lights indicate first monitored
limit to open.
Silence alarm button de-energizes
first-out alarm circuit.
Reset Required light indicates Tele-Fault II
requires reset.
Power Interruption light indicates 115V
power supply has been interrupted.
Reset light indicates Tele-Fault II is
operational.
Reset button silences alarm and resets
Tele-Fault II.
Printable Literature
Tele-Fault II 8966 Brochure

Motor-driven Multi-Burner igniter control. Automatically fires up to 40 burners in seconds!
Features:
Improved Safety and Performance:
One unit automatically fires up a complete network of gas burners in ovens,
furnaces, boilers and heat treating systems.
High-Speed Spark Ignition:
40 burners within 3 seconds
No Spark Gap Loss:
Positive contact-wiper switching design eliminates arcing gap and wasted
energy. - puts full voltage spark at burner!
Interchangeable Components:
When systems are enlarged, Rotor unit and spark electrode end plates can
be replaced with higher capacity units to accommodate additional burners.
How it works
When the Ignitifier is energized by a START button, a motorized double-end
shaft rotates its wiping contact against a series of stationary contact tips
(one for each Ignitor in the system). This causes a high voltage impulse from an
ignition transformer to be fed to each burner spark electrode, and immediately
ignites the gas-air mixture of each burner position (gas-air mixture has been
simultaneously released with actuation of the START button). The unit repeats
until all burners are ignited.
Printable Literature
Ignitifier I 5909N Brochure