The DETACTOGYR flame supervision system consists of the UV flame safeguard LFE50 and the flame detectors QRA50/ QRA51 It is designed for UV supervision and can therefore be used in connection with oil burners, gas burners and gas / oil burners. Automatic startup and control of these burners must be ensured with a control unit LEC1 (refer to Data Sheet N7761). The system is also suited for the supervision of manually operated burners.
Prerequisite for the use of the DETACTOGYR system is sufficiently high UV radiation at the flame detector’s mounting location.
For combustion plant where heat generation must also be ensured in the event the flame supervision system fails, active redundancy circuitry can be accomplished by using 2 DETACTOGYR systems.
Printable Literature
LFE50 PDF Data sheet